Panel Coolers, Panel Cooler, Panel Cooling, Panel Air Conditioner, Cabinet Enclosure Coolers, Electrical Panel Air Conditioners, Cabinet Cooling, Cooler Master Cabinet, Panel Cooler Manufactures, Panel Coolers Air Conditioner, Air Conditioner, Electronic Cabinet Cooling, Electrical Panel Coolers, How to Cool Electrical Enclosures, Panel Coolers Manufacturers, Electronic Temperature Control, Adjustable Thermostat

 

Cabinet Enclosure Cooler For Electronic Control Panel Coolers


Calculating Heat Load In Your Electrical/Electronic Panel Enclosure:

Total heat load consists of the heat transfer from outside your panel and from the heat dissipated inside the control unit.

Useful terms and conversions:

1 BTU/hr = 0.293 watts
1 BTU/hr - 0.000393 horsepower
1 Watt = 3.415 BTU/hr
1 horsepower = 2544 BTU/hr
1 Watt = 0.00134 horsepower
1 Square Foot = 0.0929 square meters
1 Square Meter = 10.76 square foot

Typical fan capacity:

4" fan: 100 CFM (2832 LPM)
6" fan: 220 CFM (6230 LPM)
8" fan: 340 CFM (9628 LPM)
10" fan 550 CFM (15574 LPM)

BTU/hr. cooling effect from fan 1.08 x (temp. inside panel in ºF - temp. outside panel in degrees F) x CFM.

Watts cooling effect from fan: 0.16 x (temp. inside panel in ºC - temp. outside panel in degrees C) x LPM.

Calculating BTU/hr. or Watts:

  1. Determine the heat generated inside the enclosure. Approximations may be necessary. For example, if you know the power generated inside the unit, assume 10% of the energy is dissipated as heat.
  2. For heat transfer from the outside, calculate the area exposed to the atmosphere except for the top of the control panel.
  3. Choose the internal temperature you wish to have, and choose the temperature difference between it and the maximum external temperature expected.
  4. From the conversion table that follows, determine the BTU/hr. per square foot (or watts per square meter) for the temperature difference.
  5. Multiply the panel surface area times the BTU/hr. per square foot (or watts per square meter) to get the external heat transfer in BTU/hr or in watts.
  6. Sum the internal and external heat loads calculated.
  7. If you do not know the power used in the enclosure but you can measure temperatures, then measure the temperature difference between the outside at current temperature, and the present internal cabinet temperature.
  8. Note size and number of any external fans. Provide this information to Nex Flow™ to assist in sizing the appropriate cooling system.
Temperature Difference in ºF
BTU/hr./sq. ft.
Temperature Difference in ºC
Watts/sq.m
5
1.5
3
5.2
10
3.3
6
11.3
15
5.1
9
17.6
20
7.1
12
24.4
25
9.1
15
31.4
30
11.3
18
39.5
35
13.8
21
47.7
40
16.2
24
55.6

Example:

The control panel coolers has two frequency drives totaling 10 horsepower and one module rated at 100 watts. The maximum outside temperature expected is 105ºF or 40.5ºC. The area of the control panel cooler exposed sides, except for the top is 42 square feet or 3.9 square meters. We want the internal temperature to be 95ºF or 35ºC.

Total internal power is 10 hp x 746 watts/hp - 7460 plus 100 watts = 7560 watts.
Assume 10% forms heat = an internal heat load of 756 watts.

Or

Total internal power is 10 hp x 2544 BTU/hp = 25440 BTU/hr plus 100 watts x 3.415 BTU/hr/watt = 25782 BTU/hr.

Assume 10% forms heat = an internal heat load of 2578 BTU/hr.

External heat load: The temperature difference between the desired temperature and the outside is 10ºF or 5.5ºC. Using the conversions (and interpolating where necessary) we multiply the area by the conversion factor:

42 sq. ft x 3.3 - 139 BTU/hr or 3.9 sq. m x 10.3 = 40 watts

Total Heat Load: 756 + 40 - 796 watts or 2578 + 139 - 2717 BTU/hr.

You would use a Model 61040 for constant operation or a Model 63040 for one-off control. (Rated at 2900 BTU/hr or 849 watts).